Ring Type Split-Core

Description:

A range of ring type Split-Core Current Transformers. The products are tape wrapped and are complete with 1 metre length flying leads. Primary ranges are available up to 3000A and 5A secondary. Suitable for various cable sizes.

Application: 

For installation into existing networks. The split-core allows installation without disconnecting cable or busbar circuits.

 

Technical Specification

  •  
Conform to IEC 185/BS7626 and BSEN 60044-1/IEC 60044-1.
  •  
Rated system voltage 0.72/3kV.
  •  
Ambient temperature range -30ºC to 80ºC
  •  
Insulation level 3kV for 1 minute
  •  
Continuous current, 1.2 x rated current

Range

 

Type Primary Current (A) VA Class Inside Diameter
1 100 1.5 1 32
150 5 1
200 5 1
300 5 1
2 400 5 1 45
500 5 1
600 5 1
3 800 5 1 65
1000 5 1
4 1200 5 1 85
1250 5 1
1500 5 1
1600 5 1
5 2000 5 1 105
2500 5 1
3000 5 1

Order Example

A ring type split-core current transformer, size 2 600/5A is "Ring Split-CT, 600/5

 

Dimensions

 

Size A B C D
1 32 88 12 35
2 45 95 12 30
3 65 115 12 25
4 85 145 12 30
5 105 165 12 30

Leads: 1m of 1.5mm PVC flexible cable

 
Home Contact us