| Description:
A range of ring type Split-Core Current Transformers. The products are tape wrapped and are complete with 1 metre length flying leads. Primary ranges are available up to 3000A and 5A secondary. Suitable for various cable sizes.
Application:
For installation into existing networks. The split-core allows installation without disconnecting cable or busbar circuits.
|
|
|
Conform to IEC 185/BS7626 and BSEN 60044-1/IEC 60044-1. |
|
|
Rated system voltage 0.72/3kV. |
|
|
Ambient temperature range -30ºC to 80ºC |
|
|
Insulation level 3kV for 1 minute |
|
|
Continuous current, 1.2 x rated current |
| Type |
Primary Current (A) |
VA |
Class |
Inside Diameter |
| 1 |
100 |
1.5 |
1 |
32 |
| 150 |
5 |
1 |
| 200 |
5 |
1 |
| 300 |
5 |
1 |
| 2 |
400 |
5 |
1 |
45 |
| 500 |
5 |
1 |
| 600 |
5 |
1 |
| 3 |
800 |
5 |
1 |
65 |
| 1000 |
5 |
1 |
| 4 |
1200 |
5 |
1 |
85 |
| 1250 |
5 |
1 |
| 1500 |
5 |
1 |
| 1600 |
5 |
1 |
| 5 |
2000 |
5 |
1 |
105 |
| 2500 |
5 |
1 |
| 3000 |
5 |
1 |
| A ring type split-core current transformer, size 2 600/5A is
"Ring Split-CT, 600/5 |
| Size |
A |
B |
C |
D |
| 1 |
32 |
88 |
12 |
35 |
| 2 |
45 |
95 |
12 |
30 |
| 3 |
65 |
115 |
12 |
25 |
| 4 |
85 |
145 |
12 |
30 |
| 5 |
105 |
165 |
12 |
30 |
Leads: 1m of 1.5mm PVC flexible cable
|
|