| Rated
Current |
1 or 5A (<0.2VA
/ phase purden) |
| |
Range 10-120% of
rated current |
| |
Overload 4 x rated
current continuous |
| |
50 x rated current
for 1 second |
| |
|
| Rated
Voltage |
57-500V (<
0.2VA / phase burden) |
| |
Range 80-120% of
rated voltage |
| |
Overload 1.5 x
rated voltage continuous |
| |
4 x rated voltage
for 1 second |
| |
|
| Frequency |
50 or 60Hz nominal
range |
| |
|
| Auxiliary |
115 / 230 / 400 AC
Voltage |
| |
|
| Pulsed
Output |
Normally open volt
free contact, |
| |
50V 150mA 5W AC /
DC |
| |
Pulse rate: 0.1, 1
or 10 per kWh. |
| |
Pulse duration:
250msec standard |
| |
|
| Analogue
output |
Rated value 0-1mA
into < 5k Ohms |
| |
0-20mA into % <
250k Ohms |
| |
|
| Accuracy |
Class 1 to IEC
1036 |
| |
|
| Operating Temp |
-25ºC to +70ºC |
| |
|
| Temp Coefficient |
0.01% per 1ºC |
| |
|
| Material |
Polycarbonate to
UL94VO |
| |
|
| Enclosure |
IP54 |
| |
|
| Mounting |
4 side brackets
and screws |